Detection and evaluation of macro-cracks and micro-cracking by using automated surface wave non-contact scanners
Author(s) :
Ciccarone, Charles [Auteur]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Piwakowski, Bogdan [Auteur]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Skoczylas, Frédéric [Auteur]
Laboratoire de Mécanique, Multiphysique, Multiéchelle - UMR 9013 [LaMcube]
Drelich, Radoslaw [Auteur]
Kazimierz Wielki University [UKW]
Henault, Jean-Marie [Auteur]
EDF [EDF]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Piwakowski, Bogdan [Auteur]

Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Skoczylas, Frédéric [Auteur]
Laboratoire de Mécanique, Multiphysique, Multiéchelle - UMR 9013 [LaMcube]
Drelich, Radoslaw [Auteur]
Kazimierz Wielki University [UKW]
Henault, Jean-Marie [Auteur]
EDF [EDF]
Journal title :
Academic Journal of Civil Engineering
Pages :
72-75
Publisher :
Association Universitaire de Génie Civil
Publication date :
2020
ISSN :
2680-1000
English keyword(s) :
Automated NDT
concrete
surface waves
cracks
velocity
attenuation
non-contact
concrete
surface waves
cracks
velocity
attenuation
non-contact
HAL domain(s) :
Sciences de l'ingénieur [physics]
Informatique [cs]
Physique [physics]
Informatique [cs]
Physique [physics]
English abstract : [en]
The goal of the presented work is the detection and evaluation of cracks, in the VeRCoRs mock-up which constitutes the double-wall containment building of a Nuclear Power Plant in scale 1/3. The experiments are conducted ...
Show more >The goal of the presented work is the detection and evaluation of cracks, in the VeRCoRs mock-up which constitutes the double-wall containment building of a Nuclear Power Plant in scale 1/3. The experiments are conducted in situ, on the inner wall of the VeRCoRs mock-up. The detection is performed by means of two automated scanners designed for the non-destructive non-contact control of concrete using surface waves (SW). The SW signal assures the penetration in a concrete wall between 1 to 60 cm. The scanners provide the non-contact measure which permits to avoid a modification of the concrete surface by a coupling agent and a time consuming coupling procedure. The results, obtained during pressure test in the VeRCoRs mock-up, prove that the scanner can be successfully used in the detection of micro-cracking, of cracks location, the evaluation of their opening and for in the progressive aging of the mock-up.Show less >
Show more >The goal of the presented work is the detection and evaluation of cracks, in the VeRCoRs mock-up which constitutes the double-wall containment building of a Nuclear Power Plant in scale 1/3. The experiments are conducted in situ, on the inner wall of the VeRCoRs mock-up. The detection is performed by means of two automated scanners designed for the non-destructive non-contact control of concrete using surface waves (SW). The SW signal assures the penetration in a concrete wall between 1 to 60 cm. The scanners provide the non-contact measure which permits to avoid a modification of the concrete surface by a coupling agent and a time consuming coupling procedure. The results, obtained during pressure test in the VeRCoRs mock-up, prove that the scanner can be successfully used in the detection of micro-cracking, of cracks location, the evaluation of their opening and for in the progressive aging of the mock-up.Show less >