Transparent fire protective sol-gel coating ...
Type de document :
Article dans une revue scientifique: Article original
URL permanente :
Titre :
Transparent fire protective sol-gel coating for wood panels
Auteur(s) :
Bellayer, Séverine [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Gossiaux, Alexandre [Auteur]
Duquesne, Sophie [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Dewailly, Benjamin [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Bachelet, Pierre [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Jimenez, Maude [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Gossiaux, Alexandre [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Gossiaux, Alexandre [Auteur]
Duquesne, Sophie [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Dewailly, Benjamin [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Bachelet, Pierre [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Jimenez, Maude [Auteur]
Unité Matériaux et Transformations (UMET) - UMR 8207
Gossiaux, Alexandre [Auteur]
Titre de la revue :
Polymer testing
Numéro :
110
Pagination :
107579
Date de publication :
2022-06
ISSN :
0142-9418
Discipline(s) HAL :
Chimie/Matériaux
Résumé en anglais : [en]
A transparent fire protective sol-gel coating deposited on wood has been evaluated using different fire tests, such as mass loss cone, mini single burning item and furnace tests. The heat release rate and total heat release ...
Lire la suite >A transparent fire protective sol-gel coating deposited on wood has been evaluated using different fire tests, such as mass loss cone, mini single burning item and furnace tests. The heat release rate and total heat release during combustion, but also the flame spread behavior and the thermal protection performances of the coatings have been studied. Two processes to apply the sol-gel coating on wood have been assessed to show the thickness dependence of the fire performance. When deposited as a thick coating (800 μm thick) on wood, the sol-gel coating lowers the total heat release, decreases the flame spread and greatly improves the thermal protection of the substrate.Lire moins >
Lire la suite >A transparent fire protective sol-gel coating deposited on wood has been evaluated using different fire tests, such as mass loss cone, mini single burning item and furnace tests. The heat release rate and total heat release during combustion, but also the flame spread behavior and the thermal protection performances of the coatings have been studied. Two processes to apply the sol-gel coating on wood have been assessed to show the thickness dependence of the fire performance. When deposited as a thick coating (800 μm thick) on wood, the sol-gel coating lowers the total heat release, decreases the flame spread and greatly improves the thermal protection of the substrate.Lire moins >
Langue :
Anglais
Comité de lecture :
Oui
Audience :
Internationale
Vulgarisation :
Non
Établissement(s) :
Université de Lille
CNRS
INRAE
ENSCL
CNRS
INRAE
ENSCL
Collections :
Équipe(s) de recherche :
Procédés de Recyclage et de Fonctionnalisation (PReF)
Date de dépôt :
2022-12-07T13:03:12Z
2022-12-09T06:57:57Z
2022-12-09T06:57:57Z
Fichiers
- 1-s2.0-S0142941822001040-main.pdf
- Version éditeur
- Accès libre
- Accéder au document