Detection and evaluation of macro-cracks ...
Type de document :
Compte-rendu et recension critique d'ouvrage
DOI :
Titre :
Detection and evaluation of macro-cracks and micro-cracking by using automated surface wave non-contact scanners
Auteur(s) :
Ciccarone, Charles [Auteur]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Piwakowski, Bogdan [Auteur]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Skoczylas, Frédéric [Auteur]
Laboratoire de Mécanique, Multiphysique, Multiéchelle - UMR 9013 [LaMcube]
Drelich, Radoslaw [Auteur]
Kazimierz Wielki University [UKW]
Henault, Jean-Marie [Auteur]
EDF [EDF]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Piwakowski, Bogdan [Auteur]

Institut d’Électronique, de Microélectronique et de Nanotechnologie - UMR 8520 [IEMN]
Institut d’Électronique, de Microélectronique et de Nanotechnologie - Département Opto-Acousto-Électronique - UMR 8520 [IEMN-DOAE]
Transduction, Propagation et Imagerie Acoustique - IEMN [TPIA - IEMN]
Skoczylas, Frédéric [Auteur]
Laboratoire de Mécanique, Multiphysique, Multiéchelle - UMR 9013 [LaMcube]
Drelich, Radoslaw [Auteur]
Kazimierz Wielki University [UKW]
Henault, Jean-Marie [Auteur]
EDF [EDF]
Titre de la revue :
Academic Journal of Civil Engineering
Pagination :
72-75
Éditeur :
Association Universitaire de Génie Civil
Date de publication :
2020
ISSN :
2680-1000
Mot(s)-clé(s) en anglais :
Automated NDT
concrete
surface waves
cracks
velocity
attenuation
non-contact
concrete
surface waves
cracks
velocity
attenuation
non-contact
Discipline(s) HAL :
Sciences de l'ingénieur [physics]
Informatique [cs]
Physique [physics]
Informatique [cs]
Physique [physics]
Résumé en anglais : [en]
The goal of the presented work is the detection and evaluation of cracks, in the VeRCoRs mock-up which constitutes the double-wall containment building of a Nuclear Power Plant in scale 1/3. The experiments are conducted ...
Lire la suite >The goal of the presented work is the detection and evaluation of cracks, in the VeRCoRs mock-up which constitutes the double-wall containment building of a Nuclear Power Plant in scale 1/3. The experiments are conducted in situ, on the inner wall of the VeRCoRs mock-up. The detection is performed by means of two automated scanners designed for the non-destructive non-contact control of concrete using surface waves (SW). The SW signal assures the penetration in a concrete wall between 1 to 60 cm. The scanners provide the non-contact measure which permits to avoid a modification of the concrete surface by a coupling agent and a time consuming coupling procedure. The results, obtained during pressure test in the VeRCoRs mock-up, prove that the scanner can be successfully used in the detection of micro-cracking, of cracks location, the evaluation of their opening and for in the progressive aging of the mock-up.Lire moins >
Lire la suite >The goal of the presented work is the detection and evaluation of cracks, in the VeRCoRs mock-up which constitutes the double-wall containment building of a Nuclear Power Plant in scale 1/3. The experiments are conducted in situ, on the inner wall of the VeRCoRs mock-up. The detection is performed by means of two automated scanners designed for the non-destructive non-contact control of concrete using surface waves (SW). The SW signal assures the penetration in a concrete wall between 1 to 60 cm. The scanners provide the non-contact measure which permits to avoid a modification of the concrete surface by a coupling agent and a time consuming coupling procedure. The results, obtained during pressure test in the VeRCoRs mock-up, prove that the scanner can be successfully used in the detection of micro-cracking, of cracks location, the evaluation of their opening and for in the progressive aging of the mock-up.Lire moins >
Langue :
Anglais
Vulgarisation :
Non
Source :
Fichiers
- document
- Accès libre
- Accéder au document
- 2471-Diagnobe%CC%81ton%202020-10047-2-10-20210311.pdf
- Accès libre
- Accéder au document